TechXZone

Mitsubishi Electric PUMY-SP80YKMD-AR1 9.0kW Outdoor Unit Only | 3 Phase

5/5

Mitsubishi Electric PUMY-SP80YKMD-AR1 9.0kW Outdoor Unit Only | 3 Phase

Experience the ultimate in cooling comfort with our premium selection of wholesale air conditioners. All units come with a full Australian Manufacturer’s Warranty for your peace of mind. Enjoy brand new, top-of-the-line air conditioners sourced directly from Australian stock – never a factory second in sight!

Shop with Confidence

Brand new Australian Stock
No Factory Seconds
Full Australian Manufacturer’s Warranty
Secure Online Payments

Description

9 kW Cooling
10 kW Heating

Single Fan Heat Pump VRF O/U

Specifications

SERIES PUMY-SP (Single Fan)
Model PUMY-SP80YKMD-A
Power Source Ê YKMD: Ê 3-phase 380-400-415 Ê V, 50 Hz; 3-phase 380 Ê V, 60 Hz
Cooling Capacity kW 9 .0
(Nominal)*1 Temperature Range of Cooling Power Input kW 2. 11
Current Input A 9.79 9.36 8.97 3.37 3.21 3.09
EER kW 4. 27
AEER Indoor kW W.B 3. 35
15.0 ~ 24.0 C
Outdoor D.B -5.0 ~ 52.0 C *3 *4 *5
Heating Capacity kW 1 0.0
(Nominal)*2 Temperature Range of Heating Power Input kW 2. 27
Current Input A 10.53 -10.07 9.65 3.63 3.45 3.32
COP kW 4. 41
ACOP Indoor kW W.B 3. 62
15 ~ 27 C
Outdoor D.B -20 ~ 15 C
Indoor Unit Connectable Sound Pressure Level (measured in anechoi Total Capacity 50% to 130% of Ou tdoor Unit Capacity
Model/Quantity c room) dB P10- P100/9
51/ 54
Refrigerant Piping Diameter Liquid Pipe mm (in.) 9.52 (3 /8) Flare
Gas Pipe mm (in.) 15.88 ( /8) Flare
Fan Type x Quantity Propelle r Fan _ 1
Airflow Rate m3/min 7 5
L/s 12 50
cfm 26 49
Control, Driving Mechanism DC C ontrol
Motor Output kW 0.20 _ 1
Compressor Type x Quantity Twin Rotary Herme tic Compressor _ 1
Manufacturer Mitsubishi Elec tric Corporation
Starting Method Inv erter
Motor Output kW 2 .1
Lubricant FV50S ( 1.4 litre)
External Finish External Dimension (H x W x D) mm Galvanised Steel Shee t Munsell No. 3Y 7.8/1. 1
981 _ 1,050 _ 330 (+25)
Protection Devices High Pressure Protection High Pres sure Switch
Inverter Circuit (COMP./FAN) Overcurre nt Detection, Overheat detection (Heat Sink Thermistor)
Compressor Compressor Thermisto r, Overcurrent Detectio n
Fan Motor Overheating, V oltage Protection
Refrigerant Net Weight Type x Original Charge R410A _ 3.5 kg
Control kg Electronic Ex pansion Valve
93 *5 *6 94 *7 93 *6 94 *7
Heat Exchanger Cross Fin an d Copper Tube
HIC Circuit (HIC: Heat Inter-Changer) HIC Circuit
Defrosting Method Drawing External Reversed Ref rigerant Circuit
RK0 1J091
Wiring BH79N194 BH79N195 BH79N194 BH79N195 BH79N194 BH79N195
Standard Attachment Document Installation Manual
Accessory Grounded Lead Wire
Optional Parts Joint: CMY-Y62-G-E Header: CMY-Y64/68-G-E

Package Description

Mini VRF Single Fan PUMY-SP
The PUMY-SP series allows up to 10 indoor units to be connected to a single outdoor unit, using the standard City Multi branch pipework system or via branch boxes to connect M Series and Mr Slim indoor units. This makes it an economic and efficient answer for multi-room applications, whilst also offering space saving benefits. Each size is available in both single and three phase options.

Compact and out of sight
The Mini VRF Single Fan PUMY-SP compact design has a reduced footprint with a 27% reduction in height and 25% reduction in weight, allowing it to be installed in more confined spaces compared to the dual fan model.

The reduced height (less than one metre) makes this unit suitable for installation on balconies. The weight reduction makes the unit easier facilitates easier installation and transportation.


Flexible connection
The outdoor unit allows piping from any four directions; front, back, bottom, or right. This enables easier horizontal connection for collective layout. The outdoor unit with an expanded piping layout improves piping workability.

Super quiet mode*
Noise level can be reduced up to 10dB(A). This allows you to operate the unit even in the night in a residential zone.

* Capacity reduction differs by mode setting. PAC-SC36NA-E is required to activate Super Quiet mode by external input.

External static pressure of 30Pa
The installation location is flexible, thanks to the 30Pa static pressure. An external static pressure of 30Pa allows outdoor unit to be installed on balconies in high-rise building or spaces near louvers.

Energy efficiency
Despite its compact size and low weight, the new Mini VRF Single Fan PUMY-SP features high efficiency.

Connectivity
Mini VRF Single Fan PUMY-SP single-fan units can be connected to the indoor units of Residential M Series and Commercial Mr Slim and CITY MULTI series using PAC-MK-BC branch boxes.

It’s possible to mix and match Residential and Commercial indoor units, providing great flexibility for solving system design challenges.


Read more

Explore More Products